CASE STUDY · HEALTHCARE

Hospital HVAC optimization at NYC Cancer Center

A dynamic condenser water temperature reset reduced chilled water plant energy by 5.9% at a New York City cancer hospital. The savings were validated through Con Edison's RTEM pilot.

Red-brick hospital building with a curved canopy entrance and large windows, seen from the street under a blue sky
NYC Cancer Center, New York City
Specialist cancer treatment hospital
Location
New York City, USA
Sector
Healthcare
Plant capacity
1,200 TR
M&V period
12 months
Validation
Con Edison RTEM pilot

Energy saving

5.9%

Reduction in chilled water plant energy, measured over 12 months

Energy saved

63,077kWh

Per year across the 1,200 TR chiller plant

Carbon avoided

26tCO2

Per year, at 0.41 tCO2/MWh

Strategies changed

1

Dynamic condenser water temperature reset only

The challenge

HVAC is the largest energy use in most hospitals. Across US inpatient facilities it accounts for about 52% of total energy (space heating 29%, ventilation 12% and cooling 11%), based on CBECS data analyzed by Bawaneh et al. (2019), Energies. This figure is a national average, not this site's metered share.

At this New York City cancer center, the 1,200 TR chiller plant ran with static condenser water temperature setpoints that didn't respond to ambient wet-bulb conditions.

Patient safety and indoor air quality requirements in a hospital are non-negotiable, so any change to HVAC control had to hold strict temperature, humidity and filtration conditions.

The project changed one strategy at a live clinical site and measured the result over 12 months.

Site profile

Facility type
Specialist cancer treatment hospital
Location
New York City, New York, USA
Chiller plant capacity
1,200 TR
Strategy
Dynamic condenser water temperature reset
M&V
IPMVP Option B, 12 months, baseline model fit R² = 0.987
Utility program
Con Edison's RTEM pilot (separate from NYSERDA's RTEM program)
Capital expenditure
Nil, software-only engagement
Carbon factor
0.41 tCO2/MWh, as used in the M&V
Site
NYC Cancer Center, New York City

Verified results

Measured over 12 months and validated through Con Edison's RTEM pilot

Savings were measured over a 12-month IPMVP Option B reporting period against a baseline model of plant energy as a function of cooling load and ambient wet-bulb temperature. R² describes how well that baseline model fits the measured data. Carbon is converted at 0.41 tCO2/MWh. No cost saving is reported for this site.

OutcomeVerified resultStatus
Energy saving5.9% reduction in chilled water plant energyVerified
Annual kWh savings63,077 kWh per yearVerified
Carbon avoided26 tCO2 per yearVerified
Baseline model fitR² = 0.987 (12-month IPMVP Option B regression)Verified
Utility validationValidated through Con Edison's RTEM pilotVerified

Verified: measured under IPMVP Option B over 12 months and validated through Con Edison's RTEM pilot.

The Exergenics approach

One strategy at a live clinical site

This project used a single strategy, the Dynamic Condenser Water Reset option. Exergenics generated the reset algorithm from the plant's own data, and it was implemented in the facility's existing BMS. Exergenics doesn't write to the BMS.

1

Set the clinical boundaries first

Temperature ranges, humidity tolerances and failsafe conditions for the clinical environment went into the model as constraints, so the strategy stays inside the limits the hospital requires.

2

Dynamic condenser water reset

The algorithm sets the condenser water temperature setpoint from ambient wet-bulb conditions and chiller load. That reduces compressor lift and plant energy without changing the chilled water supply temperature.

3

Measure for 12 months

Savings were measured over a 12-month IPMVP Option B reporting period. The baseline regression model fit the measured data with an R² of 0.987. The result was validated through Con Edison's RTEM pilot.

Optimize your healthcare facility's HVAC energy

Exergenics delivers measured HVAC energy savings for hospitals and healthcare facilities, with no capital expenditure and within the limits of the clinical environment.

Verified figures come from a 12-month IPMVP Option B measurement and verification study, validated through Con Edison's RTEM pilot.